SR-E-8DC-DA-R

Expansion module
Power supply: DC 12-24V
Input: 4 DI/AI(0-10V)
Output: 4 Relay
High Quality
CE Certified
Fast Delivery
OEM/ODM
Global Export
Professional Service

SR-E-8DC-DA-R is an expansion module for SR series CPUs adding 4 configurable DI/AI channels (0-10V) and 4 relay outputs — analog sensing plus outputs in one module.

Specifications

Technical Index

Power supply:

Nominal voltage

DC 12-24V

Operating limits

DC 10.8-28.8V

Immunity from micro power cuts

Typ.5 ms

Max. Startup current

Max. 0.4A

Max. absorbed power

0.25 A (10.8V dc); 0.28 A (28.8V dc)

Protection against polarity inversions

Yes

Input parameters:

Input No

4 (I1-I4)

Digital input

4 (I1-I4)

Analogue input

4 (I1-I4) (0..10V DC)

Inputs used as digital inputs (I1-I4)

Input voltage

DC0-28.8V

Input signal0

< 5V DC;<0.09mA

Input signal1

> 8 V DC;>0.15mA

Input current

0.16mA @ 10.8V dc

0.18mA @ 12.0 V dc

0.35mA @ 24 V dc

0.41mA @ 28.8 V dc

Response time

DC12-24V

0 to 1: Typ. 5 ms;

1 to 0: Typ. 5 ms

AC24V

0 to 1:Typ. 40ms

1 to 0:Typ. 40ms

Maximum counting frequency

Typ.:4 HZ

Sensor type

Contact or 3-wire PNP

Input type

Resistive

Isolation between power supply and inputs

None

Isolation between inputs

None

Inputs used as analog inputs (I1-I4)

Measurement range

DC 0---10V

Input impedance

Min, 24KΩ; Max. 72KΩ

Input voltage

28.8 V DC max

Resolution

9bit ,0.015V

Accuracy at 25 °C

± (Max.0.2)V

Isolation between analog channel and power supply

None

Cable length

10 m max.  shielded and twisted

Output parameters:

Output No.

4 (Q1-Q4)

Output type

Relay output

Safety certified load (resistive)

(Q1-Q2) 3A 250VAC

(Q3-Q4) 10A 250V AC

Min switching load

6V 1A

Electrical durability Expectancy

10 5 Operations at Rated Resistive Load

Mechanical life

10 7 Operations at No Load condition

Response time

Operate Time: 15 mSec. Max.

Release Time: 10 mSec. Max.

Built-in protections

Against short-circuits: None

Against over-voltages and overloads: None

Switch frequency:

Mechanism

10Hz

Resistor/light load

2Hz

Sensitive load

0.5Hz

Other parameters:

Operation temp

-20℃-+55℃

Storage temp

-40℃-+70℃

Weight

141.0g / 177.0g(packaging)

Address Setting for Expansion Modules

When multiple expansion modules are connected to one single CPU PLC, each expansion module must be assigned a distinct station address.

Factory default expansion address: 1. The expansion address is configured via DIP switch. The corresponding relationship between expansion address number and DIP switch status is shown below:

Installation Dimensions & Wiring Diagram