SR-E-8DC-DA-R
Power supply: DC 12-24V
Input: 4 DI/AI(0-10V)
Output: 4 Relay
SR-E-8DC-DA-R is an expansion module for SR series CPUs adding 4 configurable DI/AI channels (0-10V) and 4 relay outputs — analog sensing plus outputs in one module.
Specifications
|
Technical Index |
|
|
Power supply: |
|
|
Nominal voltage |
DC 12-24V |
|
Operating limits |
DC 10.8-28.8V |
|
Immunity from micro power cuts |
Typ.5 ms |
|
Max. Startup current |
Max. 0.4A |
|
Max. absorbed power |
0.25 A (10.8V dc); 0.28 A (28.8V dc) |
|
Protection against polarity inversions |
Yes |
|
Input parameters: |
|
|
Input No |
4 (I1-I4) |
|
Digital input |
4 (I1-I4) |
|
Analogue input |
4 (I1-I4) (0..10V DC) |
|
Inputs used as digital inputs (I1-I4) |
|
|
Input voltage |
DC0-28.8V |
|
Input signal0 |
< 5V DC;<0.09mA |
|
Input signal1 |
> 8 V DC;>0.15mA |
|
Input current |
0.16mA @ 10.8V dc 0.18mA @ 12.0 V dc 0.35mA @ 24 V dc 0.41mA @ 28.8 V dc |
|
Response time |
DC12-24V 0 to 1: Typ. 5 ms; 1 to 0: Typ. 5 ms AC24V 0 to 1:Typ. 40ms 1 to 0:Typ. 40ms |
|
Maximum counting frequency |
Typ.:4 HZ |
|
Sensor type |
Contact or 3-wire PNP |
|
Input type |
Resistive |
|
Isolation between power supply and inputs |
None |
|
Isolation between inputs |
None |
|
Inputs used as analog inputs (I1-I4) |
|
|
Measurement range |
DC 0---10V |
|
Input impedance |
Min, 24KΩ; Max. 72KΩ |
|
Input voltage |
28.8 V DC max |
|
Resolution |
9bit ,0.015V |
|
Accuracy at 25 °C |
± (Max.0.2)V |
|
Isolation between analog channel and power supply |
None |
|
Cable length |
10 m max. shielded and twisted |
|
Output parameters: |
|
|
Output No. |
4 (Q1-Q4) |
|
Output type |
Relay output |
|
Safety certified load (resistive) |
(Q1-Q2) 3A 250VAC (Q3-Q4) 10A 250V AC |
|
Min switching load |
6V 1A |
|
Electrical durability Expectancy |
10 5 Operations at Rated Resistive Load |
|
Mechanical life |
10 7 Operations at No Load condition |
|
Response time |
Operate Time: 15 mSec. Max. Release Time: 10 mSec. Max. |
|
Built-in protections |
Against short-circuits: None Against over-voltages and overloads: None |
|
Switch frequency: |
|
|
Mechanism |
10Hz |
|
Resistor/light load |
2Hz |
|
Sensitive load |
0.5Hz |
|
Other parameters: |
|
|
Operation temp |
-20℃-+55℃ |
|
Storage temp |
-40℃-+70℃ |
|
Weight |
141.0g / 177.0g(packaging) |
Address Setting for Expansion Modules
When multiple expansion modules are connected to one single CPU PLC, each expansion module must be assigned a distinct station address.
Factory default expansion address: 1. The expansion address is configured via DIP switch. The corresponding relationship between expansion address number and DIP switch status is shown below:
Installation Dimensions & Wiring Diagram