SR-E-8AC-R is an expansion module for SR series CPUs adding 4 AC digital inputs and 4 relay outputs — extend I/O for AC-sensed applications.
Specifications
|
Technical Index |
|
|
Power supply: |
|
|
Nominal voltage |
AC110V-240V |
|
Operating limits |
AC85 - 265 V |
|
The main frequency range |
47-63Hz |
|
Max. absorbed power |
70mA (85V ac); 40mA (265V ac) |
|
Surge Immunity |
1780V AC |
|
Protection against polarity inversions |
Yes |
|
Input parameters: |
|
|
Input No |
4 (I1-I4) |
|
Digital input |
4 (I1-I4) |
|
Analogue input |
None |
|
Input voltage |
AC110-240V |
|
Input signal0 |
AC0-40V;<0.03mA |
|
Input signal1 |
AC79-240V;>0.06mA |
|
Input Response Time |
Delay time at 0 to 1: 120V AC :Typ. 30 ms 240V AC :Typ. 20 ms Delay time at 1 to 0: 120V AC :Typ. 130 ms 240V AC :Typ. 120 ms |
|
Maximum counting frequency |
Typ. 4Hz |
|
Sensor type |
Contact or 3-wire PNP |
|
Isolation between power supply and inputs |
None |
|
Isolation between inputs |
None |
|
Protection against polarity inversions |
Yes |
|
Output parameters: |
|
|
Output No. |
4 (Q1-Q4) |
|
Output type |
Relay output |
|
Safety certified load (resistive) |
(Q1-Q2) 3A 250VAC (Q3-Q4) 10A 250VAC |
|
Min switching load |
6V 1A |
|
Electrical durability Expectancy |
10 5 Operations at Rated Resistive Load |
|
Mechanical life |
10 7 Operations at No Load condition |
|
Response time |
Operate Time: 15 mSec. Max. Release Time: 10 mSec. Max. |
|
Built-in protections |
Against short-circuits: None Against over-voltages and overloads: None |
|
Switch frequency: |
|
|
Mechanism |
10Hz |
|
Resistor/light load |
2Hz |
|
Sensitive load |
0.5Hz |
|
Other parameters: |
|
|
Operation temp |
-20℃-+55℃ |
|
Storage temp |
-40℃-+70℃ |
|
Weight |
144.7g / 180.7g(packaging) |
Address Setting for Expansion Modules
When multiple expansion modules are connected to one single CPU PLC, each expansion module must be assigned a distinct station address.
Factory default expansion address: 1. The expansion address is configured via DIP switch. The corresponding relationship between expansion address number and DIP switch status is shown below:
Installation Dimensions & Wiring Diagram