SR-E-8AC-R

Expansion module
Power supply: AC110V-240V
Input: 4 DI(AC)
Output: 4 Relay
High Quality
CE Certified
Fast Delivery
OEM/ODM
Global Export
Professional Service

SR-E-8AC-R is an expansion module for SR series CPUs adding 4 AC digital inputs and 4 relay outputs — extend I/O for AC-sensed applications.

Specifications

Technical Index

Power supply:

Nominal voltage

AC110V-240V

Operating limits

AC85 - 265 V

The main frequency range

47-63Hz

Max. absorbed power

70mA (85V ac); 40mA (265V ac)

Surge Immunity

1780V AC

Protection against polarity inversions

Yes

Input parameters:

Input No

4 (I1-I4)

Digital input

4 (I1-I4)

Analogue input

None

Input voltage

AC110-240V

Input signal0

AC0-40V;<0.03mA

Input signal1

AC79-240V;>0.06mA

Input Response Time

Delay time at 0 to 1:

120V AC :Typ. 30 ms

240V AC :Typ. 20 ms

Delay time at 1 to 0:

120V AC :Typ. 130 ms

240V AC :Typ. 120 ms

Maximum counting frequency

Typ. 4Hz

Sensor type

Contact or 3-wire PNP

Isolation between power supply and inputs

None

Isolation between inputs

None

Protection against polarity inversions

Yes

Output parameters:

Output No.

4 (Q1-Q4)

Output type

Relay output

Safety certified load (resistive)

(Q1-Q2) 3A 250VAC

(Q3-Q4) 10A 250VAC

Min switching load

6V 1A

Electrical durability Expectancy

10 5 Operations at Rated Resistive Load

Mechanical life

10 7 Operations at No Load condition

Response time

Operate Time: 15 mSec. Max.

Release Time: 10 mSec. Max.

Built-in protections

Against short-circuits: None

Against over-voltages and overloads: None

Switch frequency:

Mechanism

10Hz

Resistor/light load

2Hz

Sensitive load

0.5Hz

Other parameters:

Operation temp

-20℃-+55℃

Storage temp

-40℃-+70℃

Weight

144.7g / 180.7g(packaging)

Address Setting for Expansion Modules

When multiple expansion modules are connected to one single CPU PLC, each expansion module must be assigned a distinct station address.

Factory default expansion address: 1. The expansion address is configured via DIP switch. The corresponding relationship between expansion address number and DIP switch status is shown below:

Installation Dimensions & Wiring Diagram

Download product datasheet