Specifications
|
Technical Index |
|
|
Power supply: |
|
|
Nominal voltage |
DC 12-24V |
|
Operating limits |
DC 10.8-28.8V |
|
Immunity from micro power cuts |
Typ.5 ms |
|
Max. Startup current |
Max. 0.35A |
|
Max. absorbed power |
2W |
|
Protection against polarity inversions |
Yes |
|
Input parameters: |
|
|
Input No |
None |
|
Output parameters: |
|
|
Output No |
1 (AQ1) |
|
Output signal |
DC 0…10V/ 0..20mA (Switch on the programming software) |
|
Internal value and signal relationship |
AQ*1(0..1000)= V1(0...10V)=I1(0...20mA) *= Extension Adr. |
|
Resolution |
0.01V or 0.02mA |
|
Accuracy at 25 °C |
0.02V or 0.05mA |
|
Load capacity (voltage output): |
≥650Ω |
|
Load capacity (current output): |
≤500Ω |
|
Other parameters: |
|
|
Mounting |
On 35-mm DIN rail, 4 WM wide, or wall mounting |
|
Operation temp. |
-20℃-+55℃ |
|
Storage temp. |
-40℃-+70℃ |
|
Weight |
99.7g / 135.7g(packaging) |
|
Certificate |
CE |
Address Setting for Expansion Modules
When multiple expansion modules are connected to one single CPU PLC, each expansion module must be assigned a distinct station address.
Factory default expansion address: 1. The expansion address is configured via DIP switch. The corresponding relationship between expansion address number and DIP switch status is shown below: