PR-E-PT100/PT1000 is an expansion module adding 4 PT100/PT1000 temperature inputs to PR series CPUs — precise temperature monitoring for process control.
Specifications
| Technical Index | |
|
Power supply: |
|
|
Nominal voltage |
DC 12-24V |
|
Operating limits |
DC 10.8-28.8V |
|
Immunity from micro power cuts |
Typ.5 ms |
|
Max. Startup current |
Max. 0.25A |
|
Max. absorbed power |
1 W |
|
Protection against polarity inversions |
Yes |
|
Input parameters: |
|
|
Input No |
4 (AI1 –AI4) |
|
Digital input |
None |
|
Analogue input |
4 Channels PT100/PT1000(Switch on program software) |
|
Resolution |
0.3℃ |
|
Accuracy at 25 °C |
Max. ± 1℃ |
|
Measuring range |
-50℃ to +200℃ |
|
Output parameters: |
|
|
Output No. |
None |
|
Other parameters: |
|
|
Line length (shielded and twisted) |
10 m |
|
Operation temp. |
-20℃ to 55℃ |
|
Storage temp. |
-40℃ to 70℃ |
Address Setting for Expansion Modules
When multiple expansion modules are connected to one single CPU PLC, each expansion module must be assigned a distinct station address.
Factory default expansion address: 1. The expansion address is configured via DIP switch. The corresponding relationship between expansion address number and DIP switch status is shown below:
Installation Dimensions & Wiring Diagram
Related Applications
This controller is a common fit for the machines below. Read the application case for the hardware and control logic used:
PID Temperature Control
.