PR-24AC-R
Power supply: AC110V-240V
Input: 14 DI(AC)
Output: 8 Relay
1 built-in RS485
Modbus RTU/ASCII
PR-24AC-R is a 24-point AC-powered Micro PLC with 14 AC inputs and 10 relay outputs — plenty of I/O for larger control panels, expandable as your machine grows.
GENERAL SPECIFICATIONS
Timers: 1024
Counters: 1024
Function Blocks: 1024
Operation temp.: -20℃-+55℃
Storage: -40℃-+70℃
Protection: IP20(Non-waterproof)
RTC accuracy: MAX ±2S/day
RTC Backup at 25 °C: 20 days
Program and settings Backup:10 years
Data Power-off retentivity: 10 years
Modify parameters via keypad LCD: Yes(4*16character)
Dimensions: 133*90*60(Unit:mm)
Certificate: CE
Installation: 35-DIN rail or screw for installation
Modify parameters via keypad LCD: yes
Supported programming language: FBD & Ladder
Expansion capacity: 16 modules (PR-E-16)
Password protection: 4-digit number password protection or disable program upload function
Communication interface: 1 RS232 port (COM0 – RS232 Cable) & 2 RS485 port (COM1 external - SR-RS485, COM2 built-in)
Communication protocol: Modbus RTU/ASCII
|
Technical Index |
|
|
Power supply: |
|
|
Nominal voltage |
AC110V-240V |
|
Operating limits |
AC85 - 265 V |
|
The main frequency range |
47-63Hz |
|
Max. absorbed power |
220mA (85V ac); 85mA (265V ac) |
|
Surge Immunity |
1780V AC |
|
Protection against polarity inversions |
Yes |
|
Input parameters: |
|
|
Input No |
14 |
|
Digital input |
14 (I1-IE) |
|
Analogue input |
None |
|
Input voltage |
AC110-240V |
|
Input signal0 |
AC0-40V;<0.03mA |
|
Input signal1 |
AC79-240V;>0.06mA |
|
Input Response Time |
Delay time at 0 to 1: 120V AC :Typ. 50 ms 240V AC :Typ. 30 ms Delay time at 1 to 0: 120V AC :Typ. 90 ms 240V AC :Typ.100 ms |
|
Maximum counting frequency |
Typ. 4Hz |
|
Sensor type |
Contact |
|
Isolation between power supply and inputs |
None |
|
Isolation between inputs |
None |
|
Protection against polarity inversions |
Yes |
|
Output parameters: |
|
|
Output No. |
10 (Q1-QA) |
|
Output type |
Relay output |
|
Safety certified load (resistive) |
8A 277V AC |
|
Min switching load |
6V 1A |
|
Electrical durability Expectancy |
10 5 Operations at Rated Resistive Load |
|
Mechanical life |
10 7 Operations at No Load condition |
|
Response time |
Operate Time: 15 mSec. Max. Release Time: 10 mSec. Max. |
|
Built-in protections |
Against short-circuits: None Against over-voltages and overloads: None |
|
Switch frequency: |
|
|
Resistor/light load |
2Hz |
|
Sensitive load |
0.5Hz |
|
Other parameters: |
|
|
Weight |
Approx.400g |
Installation Dimensions & Wiring Diagram