PR-23DC-PTDAI-RT-N

Ethernet PLC
Power supply: DC 24V
Input: 3 PT100 + 2 DI/AI(0-10V) + 4 DI + 4 DI/AI(0-10V/0-20mA)
Output: 2 Transistor (PNP) + 8 Relay
Ethernet, 1 built-in RS485
Modbus RTU/ASCII, Modbus TCP, MQTT, BACnet MSTP / BACnet IP
High Quality
CE Certified
Fast Delivery
OEM/ODM
Global Export
Professional Service

PR-23DC-PTDAI-RT-N is a 23-point Micro PLC with 3 PT100 temperature inputs, mixed digital/analog inputs and Modbus, MQTT and BACnet over Ethernet — built for temperature-critical processes.

Specifications

Timers: 1024

Counters: 1024

Function Blocks: 1024

Operation temp.: -20°C - +55°C

Storage: -40°C - +70°C

Protection: IP20 (Non-waterproof)

RTC accuracy  : MAX ±2S/day

RTC Backup at 25 °C: 20 days

Program and settings Backup: 10 years

Data Power-off retentivity: 10 years

Modify parameters via keypad LCD: YES

Dimensions: 133*90*60(Unit:mm)

Certificate: CE

Installation: 35-DIN rail or screw for installation

Supported programming language: FBD & Ladder

Expansion capacity: 16 modules (PR-E-16)

Password protection: 4-digit number password protection or disable program upload function

Communication interface: 1 RS232 Port (COM0 – RS232 Cable), 3 RS485 port (COM1 available via SR-RS485, C0M2&C0M3 - 2 built-in RS485 port), 1Ethernet port.

Communication protocol: Modbus RTU/ASCII, Modbus TCP

Technical Index

Power supply:

Nominal voltage

DC 24V

Operating limits

DC 20.4-28.8V

Immunity from micro power cuts

Typ.5 ms

Max. Startup current

Max. 0.3A

Max. absorbed power

10W

Protection against polarity inversions

Yes

Input parameters:

Input No

13 ( AI1-AI3, I7 - IG)

Digital input

10 ( I7-IG)

Analogue input

3 PT100(-50…200℃) + 2(I7-I8)(0…10VDC) +4(ID-IG)(0...20mA OR 0…10V DC)

PT100 inputs (AI1-AI3)

Analog input

3 channels PT100

Resolution

0.3℃

Measuring range

-50℃ to +200℃

Cable length

10m max.  shielded and twisted

Digital input and analog inputs (0...10V)10bits ( I7-I8 )

Inputs used as digital inputs ( I7-I8 )

Input voltage

DC0-28.8V

Input signal0

< 5V DC;<0.08mA

Input signal1

> 8 V DC;>0.12mA

Input current

0.16mA @ 10.8V dc

0.18mA @ 12.0 V dc

0.34mA @ 24 V dc

0.41mA @ 28.8 V dc

Response time

0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms

Maximum counting frequency

Typ.:4 HZ

Sensor type

Contact or 3-wire PNP

Input type

Resistive

Isolation between power supply and inputs

None

Isolation between inputs

None

Inputs used as analog inputs(0..10V) ( I7-I8 )

Measurement range

DC 0---10V

Input impedance

Min, 24KΩ; Max. 72KΩ

Input voltage

28.8 V DC max

Resolution

10bit ,0.01V

Accuracy at 25 °C

± (Max.0.02)V

Accuracy at 55 °C

± (Max.0.04)V

Isolation between analog channel and power supply

None

Cable length

10 m max. shielded and twisted

Digital and high speed inputs(I9--IC)

Digital inputs ( I9-IC )

Input voltage

DC0-28.8V

Input signal0

< 5V DC; <1mA

Input signal1

> 8 V DC;>1.6mA

Input current

2.1mA @ 10.8V dc

2.3mA @ 12.0 V dc

4.6 mA @ 24 V dc

5.5 mA @ 28.8 V dc

Response time

0 to 1 :<1 ms ;1 to 0 :<1 ms

High speed inputs ( I9-IC )

Maximum counting frequency

60kHZ(I9--IC)

Digital and analog(0--10V)&analog(0...20mA) (ID-IG)

Inputs used as digital inputs ( ID-IG )

Input voltage

DC0-28.8V

Input signal0

< 5V DC;<0.08mA

Input signal1

> 8 V DC;>0.12mA

Input current

0.16mA @ 10.8V dc

0.18mA @ 12.0 V dc

0.34mA @ 24 V dc

0.41mA @ 28.8 V dc

Response time

0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms

Maximum counting frequency

Typ.:4 HZ

Sensor type

Contact or 3-wire PNP

Input type

Resistive

Isolation between power supply and inputs

None

Isolation between inputs

None

Inputs used as analog inputs(0..10V) ( ID-IG )

Measurement range

DC 0---10V

Input impedance

Min, 24KΩ; Max. 72KΩ

Input voltage

28.8 V DC max

Resolution

10bit ,0.01V

Accuracy at 25 °C

± (Max.0.02)V

Accuracy at 55 °C

± (Max.0.04)V

Isolation between analog channel and power supply

None

Cable length

10 m max. shielded and twisted

Input signal0

< 5V DC;<0.08mA

Input signal1

> 8 V DC;>0.12mA

Input current

0.16mA @ 10.8V dc

0.18mA @ 12.0 V dc

0.34mA @ 24 V dc

0.41mA @ 28.8 V dc

Response time

0 to 1 :Typ. 10.5 ms ;1 to 0 :Typ. 1.5 ms

Sensor type

Contact or 3-wire PNP

Input type

Resistive

Isolation between power supply and inputs

None

Isolation between inputs

None

Inputs used as analog inputs(0..20mA) ( ID-IG )

Analogue signal

0/4….20mA current

Input impedance

260Ω

Resolution

0.02mA

Accuracy at 25 °C

0.05mA

Cycle time for analog value generation

Typ. 50 ms

Protection against polarity inversions

yes

Overvoltage protection

Yes, if the input voltage is >6.5V, this one is automatically switched on 0--10V configuration

Isolation between power supply and inputs

No

Cable length

<=30M with shielded twisted cable(sensor not isolated)

Output

Digital/Transistor output(PNP) - Q1,Q2

Breaking voltage

DC 5--30V

Nominal voltage

≤ Supply voltage

Nominal current

Max. 0.3 A per channel

Max. breaking current

0.65 A

Voltage drop

< 2 V   for I = 0.3 A (at state 1)

Response time

Make ≤ 1 ms

Release ≤ 1 ms

Frequency (Hz)

resistive load : 10 Hz

inductive load : 0.5 Hz

Built-in protections

Against overloads and short-circuits: No

Against overvoltages (*): No

Galvanic isolation

None

PWM frequency

10K HZ

PWM cyclic ratio

0  to 100 %

PWM accuracy at 120Hz

< 0.5 % (20 % ➞ 80 %) load at 10 mA

Max. Breaking current PWM

50 mA

Max. cable length PWM

20m

5A Relay 4 outputs from Q3 to Q6

Max. breaking voltage

CE:AC 250 V/DC 30 V 5A

UL:AC 250 V/DC 30 V 3A

Electrical durability Expectancy

10 5 Operations at Rated Resistive Load

Mechanical life

10 7 Operations at No Load condition

Response time

Operate Time: 15 mSec. Max.

Release Time: 10 mSec. Max.

Built-in protections

Against short-circuits: None

Against overvoltages and overloads: None

10A Relay 4 outputs from Q7 to QA

Max. breaking voltage

CE:AC 250 V/DC 30 V 10A

UL:AC 250 V/DC 28 V 5A

Max. Allowable Power Force

1250VA

Electrical durability Expectancy

10 5 Operations at Rated Resistive Load

Mechanical life

10 7 Operations at No Load condition

Response time

Operate Time: 15 mSec. Max.

Release Time: 10 mSec. Max.

Built-in protections

Against short-circuits: None

Against overvoltages and overloads: None

Communication ports parameters:

COM0_TTL port

Can be used as program port with PR-RS232&PR-USB;

Also can be convert to RS232 port with PR-RS232

Can be convert to RS485 port with PRO-RS485

Note:Need move away the expand cover to use it

Can be used as modbus master or slave

Built-in RS485 COM2

1 built-in RS485 port (Terminal A+,B-)

Can be used as modbus master or slave

Ext RS485 COM1

Need use with PR-E-RS485 module

Can be used as modbus master or slave

Ethernet port:

Built-In(10M/100M),

1.Can be used as program or communication

2.Can be used as modbus master or slave

Monitoring webserver page

Yes

Xlogic<--->Xlogic(by Ethernet)

1 xlogic works as tcp server can connect with 8 tcp client  xlogics or other tcp devices.

Xlogic<--->Ethernet/Internet:

1 xlogic works as TCP clients can connect with 8 different tcp servers separately in maximum

Other parameter

Weight

Approx.400g

Installation Dimensions & Wiring Diagram

Download product datasheet