PR-18AC-R

Micro PLC
Power supply: AC 110V-240V
Input: 12 DI(AC)
Output: 6 Relay
1 built-in RS485
Modbus RTU/ASCII
High Quality
CE Certified
Fast Delivery
OEM/ODM
Global Export
Professional Service

PR-18AC-R is an 18-point AC-powered Micro PLC with 12 AC inputs, 6 relay outputs and built-in RS485 Modbus — a dependable logic engine for pumps, HVAC panels and small OEM machines.

GENERAL SPECIFICATIONS

Timers: 1024

Counters: 1024

Function Blocks: 1024

Operation temp.: -20℃-+55℃

Storage: -40℃-+70℃

Protection: IP20 (Non-waterproof)

RTC accuracy: MAX ±2S/day

RTC Backup at 25 °C: 20 days

Program and settings Backup :10 years

Data Power-off retentivity: 10 years

Dimensions: 95*90*61(Unit:mm)

Certificate: CE

Installation: 35-DIN rail or screw for installation

Modify parameters via keypad LCD: yes

Supported programming language: FBD & Ladder

Expansion capacity: 16 modules (PR-E-16)

Password protection: 4-digit number password protection or disable program upload function

Communication interface: 1 RS232 port (COM0 – RS232 Cable) & 2 RS485 port (COM1 external - SR-RS485, COM2 built-in)

Communication protocol: Modbus RTU/ASCII

Technical Index

Power supply:

Nominal voltage

AC110V-240V

Operating limits

AC85 - 265 V

The main frequency range

47-63Hz

Max. absorbed power

170mA (85V ac); 70mA (265V ac)

Surge Immunity

1780V AC

Protection against polarity inversions

Yes

Input parameters:

Input No

12

Digital input

12 (I1-IC)

Analogue input

None

Input voltage

AC110-240V

Input signal0

AC0-40V;<0.03mA

Input signal1

AC79-240V;>0.06mA

Input Response Time

Delay time at 0 to 1:

120V AC :Typ. 50 ms

240V AC :Typ. 30 ms

Delay time at 1 to 0:

120V AC :Typ. 100 ms

240V AC :Typ.130 ms

Maximum counting frequency

Typ. 4Hz

Sensor type

Contact

Isolation between power supply and inputs

None

Isolation between inputs

None

Protection against polarity inversions

Yes

Output parameters:

Output No.

6 (Q1-Q6)

Output type

Relay output

Safety certified load (resistive)

10A 250V AC

Min switching load

6V 1A

Electrical durability Expectancy

10 5 Operations at Rated Resistive Load

Mechanical life

10 7 Operations at No Load condition

Response time

Operate Time: 15 mSec. Max.

Release Time: 10 mSec. Max.

Built-in protections

Against short-circuits: None

Against over-voltages and overloads: None

Switch frequency:

Resistor/light load

2Hz

Sensitive load

0.5Hz

Other parameters:

Weight

Approx.300g

Installation Dimensions & Wiring Diagram

Download product datasheet